High sensitivity and close to zero load shift
Excellent characteristics in temperature and balance
Small change of output voltage after large DC impulse
A variety of configuration and output characteristics
Used for leakage current detection
Item NO.:
ZCT205Product Origin:
Xiamen, China
High sensitivity 3 phase Zero phase current transformer ZCT205
Electrical SPEC
Rated Current | 50A | ||||
DC Resistance at 25℃ | 44±5Ω | ||||
Dielectric Withstanding Voltage(Hi-pot) | 2500Vrms | ||||
Output Voltage Vo | ≥17mV |
Electrical Characteristic
Item |
Rated Current(A) |
Output Voltage |
Test Conditions |
Over Leakage |
Temperature |
Dimensions |
||
|
|
|
|
|
|
ID |
OD |
HT |
ZCT201 |
30 |
4-5.1 |
lin=10mA RL=510 |
-10%~0% |
10%Max |
5.9 |
16 |
6.5 |
ZCT202 |
30 |
5.1-6 |
lin=8mA RL=750 |
-10%~0% |
10%Max |
5.8 |
15.2 |
6.1 |
ZCT203 |
50 |
17-21 |
lin=22.5mA RL=1k |
-10%~0% |
10%Max |
9.2 |
21 |
7.3 |
ZCT204 |
30 |
12-15 |
lin=22.5mA RL=1k |
-10%~0% |
10%Max |
9.8 |
20.6 |
6.5 |
ZTC205 |
30 |
12.5-15.5 |
lin=8mA RL=4.7k |
-10%~0% |
10%Max |
9.3 |
21.3 |
7.2 |
ZCT206 |
50 |
17-21 |
lin=22.5mA RL=1k |
-10%~0% |
10%Max |
12.3 |
26 |
10 |
ZCT207 |
30 |
7.5-8.5 |
lin=25mA RL=1k |
-10%~0% |
10%Max |
15.4 |
29.8 |
10 |
ZCT208 |
60 |
10.2-12.5 |
lin=20mA RL=680 |
-10%~0% |
10%Max |
7.2 |
19.4 |
7.7 |
ZCT209 |
50 |
8-11.2 |
lin=11.25mA RL=1k |
-10%~0% |
10%Max |
7 |
17.2 |
7 |
ZCT210 |
50 |
8-11.2 |
lin=11.25mA RL=1k |
-10%~0% |
10%Max |
6.8 |
16.9 |
7.9 |
ZCT211 |
50 |
8-11.2 |
lin=11.25mA RL=1k |
-10%~0% |
10%Max |
10.6 |
25.4 |
8 |
ZCT212 |
60 |
10.2-12.5 |
lin=20mA RL=680 |
-10%~0% |
10%Max |
11 |
23.5 |
8 |
ZCT213 |
60 |
≥300 |
lin=25mA RL=1k |
-10%~0% |
10%Max |
9.4 |
23.8 |
12.7 |
ZCT218 |
60 |
10.2--12.5 |
lin=25mA RL=680 |
-10%~0% |
10%Max |
7.5 |
18.9 |
7.6 |
ZCT220 |
60 |
≥300 |
lin=25mA RL=47k |
-10%~0% |
10%Max |
10.1 |
24 |
11.5 |
ZCT225 |
60 |
≥300 |
lin=25mA RL=47k |
-10%~0% |
10%Max |
10.9 |
25.5 |
9 |
ZCT401 |
100 |
17-21 |
lin=22.5mA RL=1k |
-10%~0% |
10%Max |
15 |
29.2 |
10 |
ZCT402 |
100 |
6.3-7.5 |
lin=20mA RL=370 |
-10%~0% |
10%Max |
17.5 |
35.9 |
8.8 |
ZCT403 |
250 |
17-21 |
lin=22.5mA,RL=1k |
-10%~0% |
10%Max |
29 |
51 |
12 |
ZCT404 |
250 |
17-21 |
lin=22.5mA,RL=1k |
-10%~0% |
10%Max |
32 |
55.6 |
12 |
ZCT405 |
250 |
17-21 |
lin=22.5mA,RL=1k |
-10%~0% |
10%Max |
42 |
80*69 |
20 |
ZCT406 |
630 |
17-21 |
lin=25mA,RL=1k |
-10%~0% |
10%Max |
51.3 |
84 |
26 |
ZCT407 |
800 |
17-21 |
lin=22.5mA,RL=1k |
-10%~0% |
10%Max |
51 |
96*89 |
23 |
ZCT408 |
100 |
125-150 |
lin=500mA,RL=150 |
-10%~0% |
10%Max |
19 |
36 |
11.5 |
ZCT409 |
225 |
125-150 |
lin=500mA,RL=150 |
-10%~0% |
10%Max |
24 |
42 |
12 |
ZCT410 |
400 |
125-150 |
lin=500mA,RL=150 |
-10%~0% |
10%Max |
43 |
90*74 |
16 |
ZCT411 |
800 |
120-151 |
lin=500mA,RL=150 |
-10%~0% |
10%Max |
53 |
96*89 |
23 |
Output voltage and Turns / resistor graph
Testing
Packing and Shipping
Zero phase current transformer which detects the difference between the currents flowing in a number of conductors. The current flowing to a load must equal the current flowing back from the load. If this is not the case, a potentially dangerous residual current will be flowing somewhere in the installation.
Wire lead type zero phase current transformers are easy integrated into standard PCB sub-assemblies that are compliant with IEC61008, IEC61009 and IEC62423 requirements.
We provides customized service and expertise in consulting, design and manufacturing of current transformers,RCD fused connection unit and wireless energy monitor.