High sensitivity and close to zero load shift
Excellent characteristics in temperature and balance
Small change of output voltage after large DC impulse
	A variety of configuration and output characteristics
 Used for leakage current detection 
Item NO.:
ZCT401Product Origin:
Xiamen, China
	
Zero phase current transformer which detects the difference between the currents flowing in a number of conductors. The current flowing to a load must equal the current flowing back from the load. If this is not the case, a potentially dangerous residual current will be flowing somewhere in the installation.
	
 
Wire lead type zero phase current transformers are easy integrated into standard PCB sub-assemblies that are compliant with IEC61008, IEC61009 and IEC62423 requirements.
	
	
| Rated Current | 75A | ||||
| DC Resistance at 25℃ | 68±6Ω | ||||
| Dielectric Withstanding Voltage(Hi-pot) | 2500Vrms | ||||
| Output Voltage Vo | 17-21mV | 
 
 
	
Electrical Characteristic
| Item | Rated Current(A) | 
					Output Voltage | Test Conditions | 
					Over Leakage | 
					Temperature | 
					Dimensions | ||
| 
 | 
 | 
 | 
 | 
 | 
 | ID | OD | HT | 
| ZCT201 | 30 | 4-5.1 | lin=10mA RL=510 | -10%~0% | 10%Max | 5.9 | 16 | 6.5 | 
| ZCT202 | 30 | 5.1-6 | lin=8mA RL=750 | -10%~0% | 10%Max | 5.8 | 15.2 | 6.1 | 
| ZCT203 | 50 | 17-21 | lin=22.5mA RL=1k | -10%~0% | 10%Max | 9.2 | 21 | 7.3 | 
| ZCT204 | 30 | 12-15 | lin=22.5mA RL=1k | -10%~0% | 10%Max | 9.8 | 20.6 | 6.5 | 
| ZTC205 | 30 | 12.5-15.5 | lin=8mA RL=4.7k | -10%~0% | 10%Max | 9.3 | 21.3 | 7.2 | 
| ZCT206 | 50 | 17-21 | lin=22.5mA RL=1k | -10%~0% | 10%Max | 12.3 | 26 | 10 | 
| ZCT207 | 30 | 7.5-8.5 | lin=25mA RL=1k | -10%~0% | 10%Max | 15.4 | 29.8 | 10 | 
| ZCT208 | 60 | 10.2-12.5 | lin=20mA RL=680 | -10%~0% | 10%Max | 7.2 | 19.4 | 7.7 | 
| ZCT209 | 50 | 8-11.2 | lin=11.25mA RL=1k | -10%~0% | 10%Max | 7 | 17.2 | 7 | 
| ZCT210 | 50 | 8-11.2 | lin=11.25mA RL=1k | -10%~0% | 10%Max | 6.8 | 16.9 | 7.9 | 
| ZCT211 | 50 | 8-11.2 | lin=11.25mA RL=1k | -10%~0% | 10%Max | 10.6 | 25.4 | 8 | 
| ZCT212 | 60 | 10.2-12.5 | lin=20mA RL=680 | -10%~0% | 10%Max | 11 | 23.5 | 8 | 
| ZCT213 | 60 | ≥300 | lin=25mA RL=1k | -10%~0% | 10%Max | 9.4 | 23.8 | 12.7 | 
| ZCT218 | 60 | 10.2--12.5 | lin=25mA RL=680 | -10%~0% | 10%Max | 7.5 | 18.9 | 7.6 | 
| ZCT220 | 60 | ≥300 | lin=25mA RL=47k | -10%~0% | 10%Max | 10.1 | 24 | 11.5 | 
| ZCT225 | 60 | ≥300 | lin=25mA RL=47k | -10%~0% | 10%Max | 10.9 | 25.5 | 9 | 
| ZCT401 | 100 | 17-21 | lin=22.5mA RL=1k | -10%~0% | 10%Max | 15 | 29.2 | 10 | 
| ZCT402 | 100 | 6.3-7.5 | lin=20mA RL=370 | -10%~0% | 10%Max | 17.5 | 35.9 | 8.8 | 
| ZCT403 | 250 | 17-21 | lin=22.5mA,RL=1k | -10%~0% | 10%Max | 29 | 51 | 12 | 
| ZCT404 | 250 | 17-21 | lin=22.5mA,RL=1k | -10%~0% | 10%Max | 32 | 55.6 | 12 | 
| ZCT405 | 250 | 17-21 | lin=22.5mA,RL=1k | -10%~0% | 10%Max | 42 | 80*69 | 20 | 
| ZCT406 | 630 | 17-21 | lin=25mA,RL=1k | -10%~0% | 10%Max | 51.3 | 84 | 26 | 
| ZCT407 | 800 | 17-21 | lin=22.5mA,RL=1k | -10%~0% | 10%Max | 51 | 96*89 | 23 | 
| ZCT408 | 100 | 125-150 | lin=500mA,RL=150 | -10%~0% | 10%Max | 19 | 36 | 11.5 | 
| ZCT409 | 225 | 125-150 | lin=500mA,RL=150 | -10%~0% | 10%Max | 24 | 42 | 12 | 
| ZCT410 | 400 | 125-150 | lin=500mA,RL=150 | -10%~0% | 10%Max | 43 | 90*74 | 16 | 
| ZCT411 | 800 | 120-151 | lin=500mA,RL=150 | -10%~0% | 10%Max | 53 | 96*89 | 23 | 
	
Output voltage and Turns / resistor graph
	 
 
	
	
Testing
	 
 
	
	 
 
Xiamen ZTC Technology Co., Ltd., Experts in Manufacturing and Exporting Magnetic Core, Zero Phase Current Transformer and 309 more Products. Inquire now!